Rafter Spacing, Blocking Placement for Proper Load Support of Polycarbonate
 
- Blocking is framing member that fits between rafters or studs.
 
See Structural Load page for further explanation of snow and wind load.
See Lexan Tech Data, pages 16-21, for load charts for bldg. dept.
-
See Poly Position & Attach for mid-sheet attachment, roof & wall sheets. - 25mm for 80-100 lb. load
Sheet Thickness
Rafter Spacing
35 lb. load
45 lb. load
60 lb. load
6mm
24-1/8"
every 8 ft.
every 6 ft.
every 4 ft.
6mm
48-1/4"
every 2 ft.
every 1.5 ft.
do not use
8mm
24-1/8"
not needed
every 8 ft.
every 6 ft.
8mm
48-1/4"
every 2.5 ft.
every 2 ft.
do not use
10mm
24-1/8"
not needed
every 10 ft.
every 8 ft.
10mm
48-1/4"
every 3 ft.
every 2.5 ft.
every 2 ft.
16mm
24-1/8"
not needed
not needed
not needed
16mm
48-1/4"
every 4 ft.
every 3 ft.
every 2.5 ft.
Specs for selecting thickness, rafter spacing & blocking placement to support load on roof or wall.
Load in lbs./sq. ft. Slope over 7/12 snow slides off. Spacing may be less. No specs available.
 
Bldg. dept. has snow & wind load for your area. Supporting load is factor of frame strength and poly. sheet rigidity. Follow chart and poly. will support load.
 
To allow for movement of condensation past blocking, set blocking 3/8" back from outer surface of frame, see Blocking. When using 48-1/4" on-center rafter spacing, a neoprene spacer is placed at center of blocking. This eliminates bowing of sheet, see Spacer Install.
 
Note: The sheet must be supported on all 4 edges with a minimum of 1/2" of sheet bearing on the frame. When using sheets that have been cut along the width, and no longer have a rib at the edge, position so first rib is supported by a minimum of 1/2" of frame.
-